HP33SM Subrack Modular UPS Series (10kVA-150kVA)
TECHNICAL SPECIFAICATION
|
MODULE MODEL |
HP33SM-RM-10 |
CABINET MODEL |
HP33SM-20 |
HP33SM-40 |
HP33SM-60 |
Cabinet capacity |
10kVA~20kVA |
10kVA~40kVA |
10kVA~60kVA |
Module capacity |
10kVA |
Max. number |
2 |
4 |
6 |
MODULE MODEL |
HP33SM-RM-15 |
CABINET MODEL |
HP33SM-30 |
HP33SM-60 |
HP33SM-90 |
Cabinet capacity |
15kVA~30kVA |
15kVA~60kVA |
15kVA~90kVA |
Module capacity |
15kVA |
Max. number |
2 |
4 |
6 |
MODULE MODEL |
HP33SM-RM-20 |
CABINET MODEL |
HP33SM-40 |
HP33SM-80 |
HP33SM-120 |
Cabinet capacity |
20kVA~40kVA |
20kVA~80kVA |
20kVA~120kVA |
Module capacity |
20kVA |
Max. number |
2 |
4 |
6 |
MODULE MODEL |
HP33SM-RM-25 |
CABINET MODEL |
HP33SM-50 |
HP33SM-100 |
HP33SM-150 |
Cabinet capacity |
25kVA~50kVA |
25kVA~100kVA |
25kVA~150kVA |
Module capacity |
25kVA |
Max. number |
2 |
4 |
6 |
MODULE MODEL |
HP33SM-RM-30 |
CABINET MODEL |
HP33SM-60 |
HP33SM-120 |
HP33SM-180 |
Cabinet capacity |
30kVA~60kVA |
30kVA~120kVA |
30kVA~180kVA |
Module capacity |
30kVA |
Max. number |
2 |
4 |
6 |
INPUT |
Voltage |
380/400/415Vac, (3Ph+N+PE) |
Operating voltage range |
138~305Vac for 40% load; 305~485Vac for 100% load |
Operating frequency range |
40Hz~70Hz |
Power factor |
≥0.99 |
Harmonic distortion (THDi) |
≤3% (100% Linear load) |
Bypass voltage range |
Max. voltage: 220V: +25% (Optional +10%, +15%, +20%)
230V: +20% (Optional +10%, +15%)
240V: +15% (Optional +10%)
Min. voltage: -45% (Optional -10%, -15% -20%, -30%)
|
Bypass frequency range |
Frequency protection range: ±10% |
Power walk in |
Support |
Generator input |
Support |
OUTPUT |
Rated voltage |
380/400/415Vac, (3Ph+N+PE) |
Power factor |
1.0 |
Voltage regulation |
±1% |
Output frequency |
Line mode |
Synchronize with input, when the input frequency >±10%(±1%/±2%/±4%/±5% optional), output 50/60 (±0.1Hz) |
Bat. mode |
(50/60±0.1%)Hz |
Crest factor |
3:1 |
Harmonic distortion (THDv) |
≤1% with linear load; ≤3% with nonlinear load |
Efficiency |
Up to 95.8% |
BATTERY |
Battery voltage |
±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs, 36pcs default, 36~50pcs output power factor 1.0, 32~34pcs output power factor 0.9, 30pcs output power factor 0.8) |
Power module charge current |
18A (Max.) |
SYSTEM FEATURES |
Transfer time |
Utility to Battery: 0ms; Utility to Bypass: 0ms |
Overload |
Inverter mode |
≤110% 60min, ≤125% 10min, ≤150% 1min, >150% 1.2s shut down inverter |
Bypass mode |
30℃: 135% for long term; 40℃: 125% for long term; >1000%, 100ms |
Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
Low battery voltage |
Alarm and Switch off |
Self-diagnostics |
Upon Power On and Software Control |
Backfeed protection |
Support |
EPO (Optional) |
Shut down UPS immediately (Turn to bypass optional) |
Battery |
Advanced Battery Management |
Noise suppression |
Complies with EN62040-3 |
Audible & visual alarms |
Line Failure, Battery Low, Overload, System Fault |
Status LED & LCD display |
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault |
Reading on the LCD display |
Input, Output, Battery, Command, Setting, Maintenance |
Communication interface (Optional)
|
RS232, RS485, Parallel, LBS, Dry contact port, Relay card, SNMP card , Battery temperature sensor
|
ENVIRONMENTAL |
Operating temperature |
0℃~40℃ |
Storage temperature |
-25℃~55℃ |
Humidity range |
0~95% (Non condensing) |
Altitude |
<1000m, derating required when >1000m |
Noise level |
<58dB |
<60dB |
<62dB |
PHYSICAL |
Dimension W×D×H |
UPS cabinet |
485×850×353mm (8U) |
485×850×575mm (13U) |
485×850×752mm (17U) |
Power module |
440×620×86mm (2U) |
Net weight |
UPS cabinet |
69kg |
79kg |
98kg |
Power module |
10kVA: 19kg; 15~30kVA: 21kg |
STANDARDS |
Safety |
IEC/EN 62040-1, IEC/EN 62477-1 |
EMC |
IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11) |